Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
Programming
Page 6-32 5 July 2001 Issue 2.7
The following table lists all of the programmable non-network parameters. The defaults
listed are for Australian operation. The previous section lists items that have defaults
specific to New Zealand operation.
Item Options Default
Access Codes Qty 1-10 1 (User 0)
6 Digits 000000 (User 0)
Autotest Time Time 9:00am
Autotest Inhibit Dates For No Test Stat Holidays, weekends
Autotest Alarm Alarm Test Yes/No No alarm test
FIP MCP Zone, Disable Zone 1, Enabled
FFCIF Type 2/3 Type 3
FFCIF Mode MAF Zones Only/ MAF Zones Only
All Zones/Disabled
FFCIF RZDU Remote Ack Enabled/Disabled Enabled
FFCIF Auto Ack Enabled/Disabled Disabled
FFCIF Alarm Bells Enabled/Disabled Disabled
FFCIF Display Cause Enabled/Disabled Disabled
FFCIF always flash non-maf Enabled/Disabled Disabled
alarm LEDs
FFCIF always send non-maf alarm Enabled/Disabled Disabled
to RDU
All zones isolated = Standby Standby operate/not operate operates
Brig Test Operate/Not MAF Alarm Relay Operates Alm Relay (V2.07
or earlier)
No operation (V2.08 or later)
Printer Lines Per Page 60
Baud Rate 9600
Print Relay Operates Enabled
Event printing Enabled
Printer and history Event type selections for
history & printer -
- zone, system, sys run,
circuit, point, relay. All types enabled
Coder (NSW Cty) Disabled/1-6 Pulses Disabled
Daylight saving start Start time/date/diff Last SUN, OCT, 2am, 1 hr
Daylight saving end End time/date/diff Last SUN, MAR, 3am, 1 hr
Mains 50/60Hz 50/60Hz 50Hz
Mains fault is fault after 8 hours Enable/Disable Disabled
Battery low monitor Enable/Disable Disabled
Battery connection monitor Enable/Disable Disabled
Hourly battery test Enable/Disable Disabled
Daily 40 minute battery test Enable/Disable Disabled
Charger high/low = Fault Enable/Disable Disabled
Alarm buzzer Enable/Disable Enabled
Zone fault buzzer Enable/Disable Enabled
System fault buzzer Enable/Disable Enabled
Buzzer for non-MAF zone faults Enable/Disable Disabled
Fault sounder after 8 hours fault Enable/Disable Disabled
Fault sounder after 8 hours isolate Enable/Disable Disabled
TABLE 6.4.1
PROGRAMMABLE PARAMETERS
Continued .......