Tyco F3200 Smoke Alarm User Manual


 
Document No: LT0122 F3200 Installation & Programming Manual
New Zealand Operation
Issue 2.7 5 July 2001 Page 12-17
Outputs ┌────────────┬─┬─┬─┬─┬───────────────┐
└─┴─┴─┴─┘
spare 1├─┐ 0 Volt ┌─┤
anc defect 2├─┤ ├─┤
anc fire 3├─┤ 26 way FRC ├─┤
fire led 4├─┤ ┌────────────┐ ├─┤
defect led 5├─┤ └───── ─────┘ ├─┤
normal led 6├─┤ ├─┤
Lamp- 7├─┤ ├─┤
Lamp+ 8├─┤ ├─┤
├─┘ +24 Volt └─┤
┌─┬─┬─┬─┐
└────────────┴─┴─┴─┴─┴───────────────┘
FIG 12.8.5
Terminations from NZ mode Display Extender Board on
unprotected termination board (PA0483).
NOTE:
Sprinkler Operated and Trial Evac share the same input and are electrically connected on
the Display Extender Board. On an F4000, input 10 is used as Brigade Test and Services
Restore (BSR) is not provided.
Inputs
16 Sprinkler Operated
15 Trial evac
14 Silence alarms
13 Ext defect
12 Lamp test
11 Brigade Isol/Test
10 BSR
9 Evac Defect