F3200 Installation & Programming Manual Document No: LT0122
Applications
Page 9-26 5 July 2001 Issue 2.7
6 TERMINAL ISOLATED REPEATER (CONTINUED)
Programming & Limitations
All detector types require the circuit to be programmed for Mode 1 (Std) with voltage band
B1 programmed as Alarm.
The open collector must be programmed as OCn = ^ZnR, or the Relay must be programmed
as Rn = ZnR (i.e. Zone n not in Reset or Zone n in Reset respectively).
There can be no differentiation of voltage bands (B1, B2, B3) i.e. the FIP cannot
differentiate
between MCP and detector operation on the same circuit.
Any alarm on the detector circuit (either a short circuit or detector operation) will cause a B1
or a B2 voltage level on the FIP AZC, depending on the battery voltage.
Detector quantity and circuit length limits are shown in Table 9.4.3.
GAS GROUP 11A OR 11B GAS GROUP 11C
DETECTOR
CCT LENGTH CCT LENGTH
TYPE PART BASE
QTY
1.0mm² 0.75mm²
QTY
1.00mm² 0.75mm²
SMOKE C29BEx Z94C 40(M) 3km(R) 2.2km(R) 40(M) 0.9km(C) 0.9km(C)
(100Ω)(100Ω)
(90nF) (90nF)
33 0.97km(C) 0.97km(C)
(97nF) (97nF)
20 1.1km(C) 1.1km(C)
(110nF) (110nF)
1 1.3km(C) 1.3km(C)
(130nF) (130nF)
FLAME R24BEx - 7(M) 1.5km(R) 1.1km(R) 2(M) 1.2km(C) 1.1km(R)
(50Ω)(50Ω) (120nF) (50Ω)
HEAT FW105 - - - - - 1.3km TOT 1.3km TOT
(100Ω TOT) (100Ω TOT)
(130nF) (130nF)
40(M) 3km(R) 2.2km(R) 40(M) 1.3km(C) 1.3km(C)
HEAT T54B -
(100Ω)(100Ω)
(130nF) (130nF)
HEAT T56B Z500N 40(M) 3km(R) 2.2km(R) 40(M) 1.13KM(C) 1.3km(C)
(100Ω)(100Ω) (130nF) (130nF)
HEAT S231i+ - 11(M) 3KM (R) 2.2KM (R) 11(M) 1.13km(C) 1.13KM(C)
(100Ω)(100Ω) (113nF) (113nF)
5 1.22km(C) 1.22km(C)
(122nF) (122nF)
1 1.28km(C) 1.28km(C)
(128nF) (128nF)
FLAME S121 - 40(M) 3km(R) 2.2km(R) 32(M) 0.02km(C) 0.02km(C)
(100Ω)(100Ω)
(2nF) (2nF)
20 0.5km(C) 0.5km(C)
(50nF) (50nF)
10 0.9km(C) 0.9km(C)
(90nF) (90nF)
1 1.26km(C) 1.26km(C)
(126nF) (126nF)
FLAME MS302Ex M300 40(M) 3km(R) 2.2km(R) 40(M) 0.7km(C) 0.7km(C)
(100Ω)(100Ω)
(70nF) (70nF)
20 1km(C) 1km(C)
(100nF) (100nF)
1 1.28km(C) 1.28km(C)
(128nF) (128nF)
ION MF301Ex M300 40(M) (SAME AS MS302Ex)
PHOTO MR301Ex M300 40(M) (SAME AS MS302Ex)
HPO MR301TEx M300 40(M) (SAME AS MS302Ex)
TABLE 9.4.3
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 6-TERMINAL REPEATER