Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
Programming
Page 6-28 5 July 2001 Issue 2.7
GLOBAL DATA (CONTINUED)
The following table indicates suitable settings:
COUNTRY/STATE FORWARD BACKWARD
ENABLE
D
MONTH
SUNDA
Y
HOUR MONTH
SUNDA
Y
HOUR
NSW, ACT, VIC, SA Y 10 L 2 3 L 3
TAS (1) Y 10 L 2 3 L 3
NZ Y 10 1 2 3 3 2
WA, NT, QLD (2) N - - - - - -
NOTE: (1) Tasmania may start Daylight Saving earlier at their discretion.
(2) WA, NT and QLD do not have Daylight Saving.
Mains/Battery Options
Most of these options are available only in V2.07 or later software and are intended for
installations which have to meet the requirements of the Australian Standard AS4428.1
1998.
Mains fail = fault after 8 hours
If this is enabled, then when mains has been failed continuously for 8 hours a fault will be
signalled.
Charger fault monitor – if enabled, signals a fault when the charger is high or low.
Battery low monitoring – if enabled, a fault is signalled when a battery low voltage occurs.
For a slimline NDU with no MAF board, the battery very low threshold is used as the battery
low threshold. Battery low monitoring and battery connection tests are not required for
AS1603.4 but are required for AS4428.1.
Battery connection test – if enabled, the battery connection will be checked every 30
seconds by reducing the charger voltage.
Hourly battery capacity test – if enabled, a 60 second battery test will be done automatically
on the hour.
Daily battery capacity test – if enabled, a 40 minute battery test will be done automatically at
the start of the daily auto test or at 9am if there is no auto test. WARNING: older versions of
F3200 must have the battery test resistors R52, R53 removed from the MAF board if this test
is enabled.
Keys Enable
V2.06 or earlier software
V2.06 or earlier software allows two specific keys – BELLS ISOL and ANCIL ISOL- to be
programmed as enabled or disabled. When disabled, the key will be ignored but the isolate
functions that are normally accessible with these keys can be done using zones 193 to 197.