F3200 Installation & Programming Manual Document No: LT0122
Programming
Page 6-22 5 July 2001 Issue 2.7
TEXT PROGRAMMING WITH A PC (CONTINUED)
I0
JEH (three characters)
I1
MJS
.
.
I9
BAC
F
Phone VIGILANT FIRE 7903600 (40 characters max)
To initiate the loading of the file into the F3200 panel, enable remote text entry as described
above. Run a terminal emulation program on the PC and press ENTER on the PC.
When the message:
Enter Znn, Rnn, An, S, Tn, In, F, P, Q :
appears, send the file containing the text names to the F3200 panel using the "transmit file"
command of the terminal emulator.
If possible set the terminal emulator to use XON/XOFF flow control or else set the line
transmit delay to 100 milliseconds.
After loading the text names into F3200, do a database printout to check that all names have
been assigned correctly.
Refer to Section 6.3.4 for information on the setup of the F3200 serial port. Remember to
set the baud rate of the PC to that programmed into the F3200 for its printer port.
6.4.4 GLOBAL DATA
Option 3:Global data from the main Program menu, or Option 2:Global data from the view
menu provides a tree of menus that allow many options to be set.
The options provided in the global data menu tree depend on the version of software being
used.
There are two different menu trees listed below, the first of which is for V2.06 or earlier
software, and the second is for V2.07 and later software.
For V2.06 or earlier software
Some options shown in these menus are not available in earlier versions of software.
1:Auto Test; 2:FIP MCP Zone; 3:FFCIF Mode; 4:All zones isolated; 5:More.
Option 5:more gives the following menu.
1:Brigade Test Relay Activate; 2:Printer Setup; 3:Country Coder; 4:more
Option 4:more gives a further menu.
1:Daylight saving start 2:Daylight saving end
3:Mains 50/60Hz 4:Keys enable