Applications
Issue 2.7 5 July 2001 Page 9-25
9.4.3.2 6 TERMINAL ISOLATED REPEATER
The following 6 terminal isolating repeaters can connect an F3200 zone to an IS detection
circuit using the circuit of Figure 9.4.3.2.
Pepperl & Fuchs KHD3-ICR/Ex130 200
Pepperl & Fuchs KFD2-CR-Ex1.30 200
OR
FIG 9.4.3.2
F3200 IS CIRCUIT USING 6-TERMINAL REPEATERS
Relay or Open Collector
For each AZC there must be either: a corresponding relay (e.g. Module Relay RLn) with
normally closed contacts breaking the supply to the Isolator as shown; or an open collector
output switching the supply 0V as shown. As the open collector is standard with an 8ZM it is
the cheapest alternative.