Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
Programming System Configuration
Page 7-20 5 July 2001 Issue 2.7
7.4.3.2 Operands Type 2
ACK When the "ACK" key is pressed with the base display selected this returns true for
between 1 and 2 complete passes of all output logic equations.
ALM True if 1 or more local MAF zones is in alarm, or true in New Zealand mode if a
latched battery very low alarm is present.
BEL See discussion on Bells/Anc3 in Ancillary Relay Tokens.
Always false if Bells is isolated or silenced by network silence - otherwise , true if:
1. Non isolated zone mapped to Bells is in alarm, or
2. Bell test in progress
3. 2 second ring for Auto-reset mode for non isolated zone mapped to bells.
4. For networked systems, a network MAF alarm state received from another
panel and this panel is programmed to use it and this panel is also
programmed with "receive network bells control" enabled.
5. In New Zealand mode, true if Trial Evac operated.
BFT This is available in V2.07 or later software and is true when there is a battery
connection fault or a battery capacity fault. Note the battery connection tests and
battery capacity tests must be enabled for them to produce faults.
BGT True if the brigade test key on the local FIP or an RZDU has been held down for 2
seconds - at which point this token returns true while the key remains down (even if
the brigade test has been programmed to not operate the Brigade Alarm relay). For
networked systems, this token is not true for a brigade test initiated at another panel
on the network.
BLI Bells Isolate. For V2.07 or earlier software, BLI is true if the bells are isolated locally.
For V2.08 or later, BLI is time if the bells are isolated locally or if they are silenced by
a received network silence state. Note: for the bells to be silenced locally by a
received network silence state, this panel must have “receive network bells silence”
enabled and must also have “use MAF status” enabled for the particular SID sending
the network silence. For New Zealand mode, BLI is not set time by the local silence
alarms keyswitch (refer NSA).
BLO Battery low. True if the last battery test failed. Remains true until a successful test
has been completed. If battery low fault monitoring is enabled it will also be set true
by a battery low fault.
BSR New Zealand mode local services restore operated.
BTS True if a battery test is currently in progress.
CGF This is available in V2.07 or later software and is true when there is a charger fault
and charger fault monitoring is enabled.
FLT True if 1 or more local MAF-mapped zones or module/ancillary relays are in fault.
ISO True if 1 or more local MAF-mapped zones or module/ancillary relays are isolated.
MFL True if the mains is currently failed. If it is desired to detect a condition of mains
failed continuously for 8 hours then timer logic must be used in conjunction with this
token.
MUA True if there are 1 or more unacknowledged alarms in the FFCIF queue.
NED New Zealand mode external defect input true.