Tyco F3200 Smoke Alarm User Manual


 
Document No: LT0122 F3200 Installation & Programming Manual
Network Programming
Issue 2.7 5 July 2001 Page 11-11
NETPG4 OPTIONS (CONTINUED)
For 1-12 devices, select 8 slots
For 13-24 devices, select 16 slots
For 25 or more devices, select 32 slots
5. Mode B
This is a numeric value 0-7 which is used to control some of the network operations as
follows. This value should be changed only under instruction from a systems engineer. For
normal operation a value of 3 should be used.
Early Collision Detection
Values 0-3 enable early collision detection
Values 4-7 disable early collision detection
Message Combination
Values 0, 4 Combine no messages
Values 1, 5 Combine "ack" messages into a single network access with up to
maximum of 10 ack messages combined.
Values 2, 6 Combine application messages when possible. This includes
combining MAF status, MAF totals, Netvars and Link Integrity A and
B.
Values 3, 7 Combine both ACK messages and application messages.
11.3.5 NETPG5 OPTIONS
1. Ack broadcasts to specific SID
If this parameter is set to a non-zero SID number XYZ then this panel will send an
acknowledge to a broadcast sent by SID XYZ. If this parameter is set to zero then this
feature is disabled.
Only one device on a network (say SID XYZ), should be programmed to acknowledge all
broadcasts but it can have its own broadcasts acknowledged if another panel on the network
has "ACK broadcasts to specific SID" set to XYZ.