Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
System Specifications
Page 3-12 5 July 2001 Issue 2.7
AZC SPECIFICATIONS (CONTINUED)
Timing
Standard Delay 2.3 sec (2.0 - 2.6 sec)
(into Alarm, Fault, Normal)
AZC Reset 5.3 sec (5.0 - 5.6 sec)
AZC Ignore Period 1 2 sec nom (plus std 2.3 sec delay)
(after Reset)
AZC Ignore Period 2 1 sec nom (plus std 2.3 sec delay)
(after Start Up or Programming)
AZC Time Into Alarm Programmable 0-250 sec
AZC Time Out of Alarm Programmable 0-250 sec
Refer to Section 7.2.4 for detail on other sequences and programmable delays.
3.4.2 MAF/PSU INPUTS
Battery Termination One pair screw terminals; 4sq mm max cable
AC Input 31V rms; 3.6A rms; 2.8mm tab terminals
Door Switch 5V, 0.5mA, Unsupervised, 4 Way .1" pcb header, J6
MCP 5V, 1mA, 2k7 EOLR, 4 Way .1" pcb header, J6
Spare Inputs (not fitted) 5V, 0.5mA, Unsupervised, Cabinet internal use only, 4 Way
.1" pcb header, J5
Relay Supervision
Anc 1 Sup/Anc 2 Sup One screw terminal each
Modes of Operation 1 Door holder (Default for Anc 1)
2 Load (Default for Anc 2)
Relay Off Relay On
Door Holder Mode expects Voltage Present No Voltage Present
Load mode expects Resistive to 0V Open Circuit or Voltage Present
Voltage Threshold 3.65V Nom
(Door Holder Mode)
Supervision Current 0mA @ +5V, 1mA @ 0V
Load Resistance 400 Ohm - 10k Ohm
(Load Mode) less than 400 Ohm with series diode at load.
14 Ohm absolute minimum.
Bells Relay
Form Reverse polarity - requires series diode at each device