Tyco F3200 Smoke Alarm User Manual


 
Document No: LT0122 F3200 Installation & Programming Manual
System Specifications
Issue 2.7 5 July 2001 Page 3-13
MAF/PSU INPUTS (CONTINUED)
End of Line Resistor No. of Circuits Type
1 3k3, 5%, 250mW resistor
2 6k8, 5%, 250mW resistor
3 10k, 5%, 250mW resistor
Supervision Current 0mA @ +5V, 1.5mA @ 0V, +ve to BELLS- terminal
Circuit Resistance 100 Ohm max.
3.4.3 CONTROLLER/DISPLAY INPUTS
Spare DC Input/Output 24Vdc nom demountable screw terminal, 4 way, J5
Spare Input 22V, 10k Ohm pull up resistor
Provision for supervision (up to 5 band)
Spare Inputs IP0, 1, 2 Unsupervised, Cabinet internal use only
(not fitted) +5V, 100k pull up resistor, 10 Way FRC header, J10
Serial I/O RZDU Refer Section 3.5.3; Others 3.5.2
3.4.4 8 RELAY MODULE SUPERVISION
Form Load monitoring
Relay Off Relay On
Expects Resistance to 0V Voltage Present
Selected By Minijump link on pcb & programming of FIP
Default Programming Disabled (unsupervised)
Load Resistance 400 Ohm - 10k Ohm
Less than 400 Ohm with series diode at load
14 Ohm absolute minimum
Voltage Threshold 3.65V nom.
Supervision Current 0mA @ +5V, 1mA @ 0V
3.4.5 NZ MODE DISPLAY EXTENDER BOARD INPUTS
The Display Extender Board is used with New Zealand operation only. The inputs it
provides are : Silence Alarms, Trial Evac, Building Services Restore, Lamp Test and
External Defect. All inputs have closure to zero volts to assert the input. An input may be
left open or unconnected if not used. Refer to section 12.8 for wiring.
All Inputs Closure below 1.5V @ 0.35mA required to activate.
Open voltage = 5V