Tyco F3200 Smoke Alarm User Manual


 
Document No: LT0122 F3200 Installation & Programming Manual
System Specifications
Issue 2.7 5 July 2001 Page 3-15
3.5.3 MAF/PSU OUTPUTS
Brigade Relays
Number 4
Standby Normally energised
De-energises on battery fail or panel fail
Fault, Isolated, Alarm Normally de-energised
Energise on active state
Form 1 Pole changeover contacts
Voltage-free
Termination Demountable screw terminals
1.5sq mm max cable
Rating ELV only
30V, 5Adc resistive
30V, 3Adc inductive
Isolation 1500V rms contact to coil
Ancillary & Bells
Number 3
Anc 1, Anc 2
1 Pole changeover contacts
Voltage-free
Termination Demountable screw terminals
1.5sq mm max cable
Rating ELV only
30V, 2Adc resistive
30V, 1Adc inductive
(Note: The relays are 2 pole, with second pole terminated on pcb pads).
Operation Programmable
Default Active on any unisolated Zone Alarm.
Supervision Separate terminal (ref 3.4.2)
Anc 3/Bells
2 pole relay
Link selectable function
Standard Format Bells
Switched 24Vdc output
2 terminals, Bells +, -
Demountable screw terminals
1.5sq mm max cable