Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
System Specifications
Page 3-14 5 July 2001 Issue 2.7
3.5 OUTPUT SPECIFICATIONS
3.5.1 8 ZONE MODULE OUTPUTS
Type Darlington open collector
Switch to 0V
Voltage Rating 28.5V max, "off" state
1V max @ 30mA, "on" state
1.1V max at 100mA
Current Rating 100mA max per O/P, 0.6A max per module
1A max per FIP.
Transient Protection Allows external wiring
Terminations 8 Way demountable screw terminal
1.5sq mm max. cable
Operation Programmable
Default O/C 1 = Zone 1 Alarm
O/C 2 = Zone 2 Alarm
etc.
3.5.2 8 RELAY MODULE OUTPUTS
Form 1 Pole changeover contacts
Voltage-free when unsupervised
Termination Demountable screw terminals
1.5sq mm max cable
Rating ELV only
30V, 2Adc resistive
30V, 1Adc inductive
Note The relays are 2 pole, with the second pole terminated on pcb pads.
Operation Programmable
Supervision Ref 3.4.4.
Looping Terminals 2 Sets of 4 joined
voltage-free terminals per module