Document No: LT0122 F3200 Installation & Programming Manual
Programming System Configuration
Issue 2.7 5 July 2001 Page 7-27
THE OUTPUT LOGIC PROGRAMMING MENUS (CONTINUED)
Open Collectors - 1 to 64 corresponding to the AZC boards installed.
Ancillary Relay - MAF ancillary relays 1,2,3.
Net Var - network variables 1 - 256 (network systems only).
Menu 2
MAF Relay - Standby, Fault, Isolate, Alarm
Zone Isol, Zone De-isol, Zone Reset - these commands can be applied to alarm
zones (zones 1-64), module relays (zones 65 - 128), ancillary relays (zones
193-196) and plant (zone 197). These are described in section 7.4.9.
free space - this option is used to display the number of free and used output logic
blocks - output logic storage memory is organised into 16 byte blocks.
Menu 3
SNA - for V2.09 or later software, this is used to control the fault sounder. When the
equation changes from false to true, the fault sounder is activated and the SOF
token becomes true. Pressing any key will silence the sounder. SNA must go
false then true again to re-activate the sounder. The fault sounder will also be
activated by any conditions in the system that normally activate it.
7.4.7 PROGRAMMING RELAYS
When programming relays, the following points should be observed:
1. The default operation of the F3200
MAF Brigade relays
conform to AS1603.4.
Programming relays for operation, other than default, may contravene the standard.
2. If programming the
Alarm relay
with a logic equation and it is desired to have it
operate during Brigade Test, then the equation entered should include the BGT
token. For network systems, note that the ALM token does not include any alarm
status received from other panels on the network.
3. Although the
MAF Standby relay
may be programmed to operate off a logic
equation, it is still de-energised (by hardware) for the Battery Very Low condition.
4. If it is desired to use the
Plant Isolate
option of the "ANCIL ISOL" function menu, all
relays to be isolated must include the PLI token in their equations. E.g. R3 = (Z5A +
Z6A) . ^PLI.
5. It is
not
recommended to program
normally energised relays
because
Global
Isolate
and
Plant Isolate
de-energise them. Also, they increase FIP quiescent
current. All relays have normally closed contacts (i.e. for relay de-energised).
6. If
Anc3
has a logic equation entered for it, it no longer operates as "Bells" and is not
affected by the
"BELLS ISOL"
key. The key does still set the BLI token and so, if
desired, another relay (e.g. a module relay) could be programmed to operate on a
logic equation which includes BEL or BLI (and hence be isolated by "BELLS ISOL").
The BELLS ISOLATED LED operates from BLI and is not affected by the
programming of Anc3.