Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
Applications
Page 9-10 5 July 2001 Issue 2.7
LOGIC & CONFIGURATION (CONTINUED)
Relay 1 = Alert O/P (1st stage sign FIRE ALARM)
Relay 2 = Evac O/P (2nd stage sign EVACUATE and DO NOT ENTER)
Relay 3 = Gas Release Solenoid
Relay 4 = System Inoperative sign
Isolate = Guard Relay (see note 2)
Timer
T1 [S30:0] = V1 30 Second time delay from "Gas Initiated" (second stage).
Variables
V1 = Z1A.Z2A.^Z5A + Z3A
Open Collector LEDs
OC1 = V1
OC2 = Z3A
OC3 = Z4A
OC4 = Z5A + OC5 + Z7A + Z4:7(1)I + Z1:7(1)F + R3F +R1I+R2I +R4I (see notes 2,9)
OC5 = Z6A+Z1:3(1)I + R3I + Guard Iso (if isolatable, see note 2)
Relays
R1 = Z1A + Z2A + Z3A + Z4A (Alert)
R2 = Z4A + V1 (Evac)
R3 = T1 (Gas Release)
R4 = OC4 (System Inoperative)
ISO (or Rn) = V1 (Guard) (see note 2)
Configure Circuits
AZC Alarm Text B1
Circuit 1 Smoke (1) -
Circuit 2 Smoke (1) -
Gas Start MCP/Manual (4) -
Gas Released FSW (3) or PSW (6) Alarm (2)
Gas Inhibit MCP/Manual (4) -
Gas Isolated MCP/Manual (4) If required (see note 3)
Lock-off Valve VMD/Valve (5) If required (see note 9)
(Circuits 1 and 2 use all default settings).
Configure Zones
Zone Latch MAF Anc1 Anc2 Bells
Circuit 1 - - - - -
Circuit 2 - - - - -
Gas Start N ? - - - - (see note 10)
Gas Released - - - - -
Gas Inhibit N N N N N
Gas Isolated N N N N N If required (see note 3)
Lock-off Valve NNNNN If required (see note 9)
(Zones 1-4 use all default settings. Zone 3 may be required to be non-latching. See note 10.)