F3200 Installation & Programming Manual Document No: LT0122
System Specifications
Page 3-18 5 July 2001 Issue 2.7
CONTROLLER/DISPLAY (CONTINUED)
Pin 2 3 5 1 4 6 7 8
Tx Rx 0V └──┴──┘ └──┘
25 Way Miniature D available via transition cable Part Number
LM0042
Female Pins (socket)
Pin 2 3 7 6 8 20
Rx Tx 0V └──┴──┘
Alternative Function (on same serial port)
Serial Port 0
10 Way FRC header, J2
UART signals: RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available
Network 1
10 Way FRC header, J7
(fitted only for network systems)
Network 2
10 Way FRC header, J9
(fitted only for network systems)
UART signals for Network 1/2
RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available
3.5.5 RS485 BOARD
CMOS Modem: 10 Way FRC header
+12V, RXD- TXD-, RTS-, CTS-, 0V, DCD-, +5V
Network: 6 Way demountable screw terminals
RS485 standard signals
A+, A-, B+, B-, 0V ISOL, Earth
3.5.6 NZ DISPLAY EXTENDER BOARD OUTPUTS
This is used in New Zealand mode only. Refer to section 12.8 for wiring of the outputs on
the unprotected termination board. The Display Extender Board already has common
Normal, Defect and Fire status LEDs fitted to it, but these may be replicated externally if
necessary. There are also ancillary defect and fire outputs which are active low open
collector, and an output to drive an index lamp.
All Outputs (except LAMP) Open collector pulldown to 0V
Off voltage = 30Vmax
On voltage = 1.1V @ 100mA (max)
On Current = 100mA max
LAMP + Open collector pull up to VBATT
Off voltage = 0V
On voltage = VBATT-1V
On current = 400mA max
LAMP - Connected to Battery –