F3200 Installation & Programming Manual Document No: LT0122
System Specifications
Page 3-10 5 July 2001 Issue 2.7
AZC SPECIFICATIONS (CONTINUED)
Detector Alarm Currents
The current available to a latched detector is the AZC supply current at the detector "Alarm"
voltage minus the EOLR current and the remaining quiescent current at that voltage.
The following graphs show current/voltage characteristics for the various modes of
operation.
GRAPH 3.4.1
AZC CURRENT LIMIT CHARACTERISTICS (MODES 1 & 2)
ICL = Current Limit
IAV = Current Available to Detectors with EOLR fitted
IAV = ICL - IEOLR
GRAPH 3.4.2
AZC CURRENT VS VOLTAGE : MODE 1 (STANDARD)