Emerson Process Management 3420 Carbon Monoxide Alarm User Manual


 
220 Digital outputs
Section 6: Meter operation Reference, Installation, and Operations Manual
June 2013 3-9000-743 Rev S
Digital output test mode
The Mark III meter provides a mode of operation for individually testing the digital output signal
pairs. Entering, configuring, and exiting this mode is accomplished by setting data points using
the Daniel MeterLink
Tools - Outputs Test screen as described in the table below.
The maximum length of time that a digital output pair can remain in the test mode is specified
via the NonNormalModeTimeout data point. Note that this data point applies to both digital
output pairs (as well as various other tests). The NonNormalModeTimeout data point can be
changed using the Daniel MeterLink
Edit/Compare Configuration screen. It can be set within the
range [1, 30 min] and has a default value of 2 min.
Table 6-13 Data points for digital outputs test
Daniel MeterLink
Display Name
Data Points, Options and Guidelines
Digital output 1
Output 1A
or
Digital output 1
Output 1B
or
Digital output 2
Output 2A
or
Digital output 2
Output 2B
Data points affected:
DO1ATestVal
DO1BTestVal
DO2ATestVal
DO2BTestVal
Options:
Select either Test Low(0) to force the corresponding output low or Test High(1) to
force the corresponding output high.
Guidelines:
The selected test value takes effect within one batch period of clicking the
Start DO1 or Start DO2 button (see below).
For options and guidelines, see timeout discussion below and Daniel MeterLink
online help.
Start(Stop) DO1
or
Start(Stop) DO2
Data points affected:
DO1PairTestEnable
DO2PairTestEnable
Options:
Click on the Start button to enter the test mode (TRUE) (Note: the Start button will
become the Stop button after clicking on it.)
Click on the Stop button to exit the test mode (FALSE) (Note: the Stop button will
become the Start button after clicking on it.)
Guidelines:
The selected test value (see above) takes effect within one batch period of clicking
the Start DO1 or Start DO2 button.
For further information, see timeout discussion below and Daniel MeterLink online
help.