124 Meter configuration using Daniel MeterLink
Section 5: Startup and meter configuration Reference, Installation, and Operations Manual
June 2013 3-9000-743 Rev S
Temperature and Pressure Page Section 5.6.12
Gas Chromatograph Setup Page Section 5.6.13
AGA8 Setup Page Section 5.6.14
Continuous Flow Analysis Page Section 5.6.15
Update Time Wizard Section 5.7.1
Table 5-11 Daniel MeterLink Field Setup Wizard
Page Description
Startup
See Section 5.6.5
Meter name
Enter an alphanumeric name for the meter. When connecting, this name can be used as the
filename for logs and reports collected. This field is only available for Daniel Mark III Ultrasonic Gas
Flow Meters.
Serial #
Enter the serial number from the meter body. This will be included in the Inspection Report of
Maintenance logs. This field is only available for Daniel Mark III Ultrasonic Gas Flow Meters.
Station Name
Enter the station name for the meter’s location. This is included in the Inspection Report of Main-
tenance logs. This field is only available for Daniel Mark III Ultrasonic Gas Flow Meters.
Address
Enter the address for the meter’s location. This is included in the Inspection Report of Mainte-
nance logs. This field is only available for Daniel Mark III Ultrasonic Gas Flow Meters.
City
Enter the city for the meter’s location. This is included in the Inspection Report of Maintenance
logs. This field is only available for Daniel Mark III Ultrasonic Gas Flow Meters.
State and country
Enter the state and country for the meter’s location. This is included in the Inspection Report of
Maintenance logs. This field is only available for Daniel Mark III Ultrasonic Gas Flow Meters.
Temperature for meter corrections
Temperature is required for flow and for meter internal diameter Temperature expansion correc-
tion. If a temperature transmitter is connected to the meter, select Live for this option. If a temper-
ature transmitter is not connected to the meter but either Base condition correction or
Temperature expansion correction is required, select Fixed. You will enter in a fixed temperature
on a later page. If neither of the corrections is required, select Not used.
Pressure for meter corrections
Pressure is required for flow and for meter internal diameter Pressure expansion correction. If a
pressure transmitter is connected to the meter, select Live for this option. If a pressure transmitter
is not connected to the meter but either Base condition correction or Pressure expansion correc-
tion is required, select Fixed. You will enter in a fixed pressure on a later page. If neither of the cor-
rections is required, select Not used.