Reference, Installation, and Operations Manual Section 5: Startup and meter configuration
3-9000-743 Rev S June 2013
Update Time Wizard 161
For controlling how batches are run, configure these data points which are displayed in the
Daniel MeterLink
Update Time Wizard (listed in the table below):
Table 5-21 Data Points for Batch Cycle Processing, or Update Time Control
Daniel MeterLink
Display Name
Data Points, Options and Guidelines
Update Rate Data points affected:
SpecBatchUpdtPeriod
Options:
Standard (1000 ms)
Rapid (250 ms)
Guidelines:
For additional guidelines, see Section 6.1.3 and Daniel MeterLink online
help.
Stack Size Data points affected:
StackSize
Options:
None (1)
2 (2)
4 (4)
8 (8)
16 (16)
Guidelines:
Stacking (i.e., stack size other than None) is only available with the Standard
update rate.
For additional guidelines, see Section 6.1.3 and Daniel MeterLink online
help.
Filter Data points affected:
Filter
Options:
Off (FALSE)
On (TRUE)
Guidelines:
Filtering is only available with the Standard update rate. It is not available with
the Rapid update rate.
For additional guidelines, see Section 6.1.3 and Daniel MeterLink online
help.