Emerson Process Management 3420 Carbon Monoxide Alarm User Manual


 
142 Current Outputs Page
Section 5: Startup and meter configuration Reference, Installation, and Operations Manual
June 2013 3-9000-743 Rev S
Maximum scale velocity:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
AO1MaxVel
AO2MaxVel
Options:
Enter a velocity value (m/sec or ft/sec)
Guidelines
This point is only used when the analog output content is either
the average flow or sound velocity.
This point specifies the (flow or sound) velocity associated with
the maximum current (20 mA).
For options and guidelines, see Section 6.2.3 and Daniel
MeterLink online help.
Minimum scale velocity:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
AO1MinVel
AO2MinVel
Options:
Enter a velocity value (m/sec or ft/sec)
Guidelines
This point is only used when the analog output content is either
the average flow or sound velocity.
This point specifies the (flow or sound) velocity associated with
the minimum current (4 mA).
For options and guidelines, see Section 6.2.3 and Daniel
MeterLink online help.
Full scale energy rate:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
AO1FullScaleEnergyRate
AO2FullScaleEnergyRate
Options:
Enter an energy rate (MJ/hr or MMBTU/hr)
Guidelines
This point is only used when the analog output content is energy
rate.
This point specifies the energy rate associated with the maximum
current (20 mA).
For options and guidelines, see Section 6.2.3 and Daniel
MeterLink online help.
Table 5-15 Data Points for Analog (Current) Output Configuration
Daniel MeterLink
Display Name
Data Points, Options and Guidelines