Emerson Process Management 3420 Carbon Monoxide Alarm User Manual


 
130 Meter configuration using Daniel MeterLink
Section 5: Startup and meter configuration Reference, Installation, and Operations Manual
June 2013 3-9000-743 Rev S
Temperature and Pressure
Page
See Section 5.6.12
The Temperature and Pressure Page allows you to set the scaling for analog inputs, enter fixed
values, and set alarm limits for both temperature and pressure. This page is only displayed if either
temperature or pressure was set to Live or Fixed on the Startup Page.
Temp eratur e
Live temperature Enabled if Live was selected for Temperature for meter corrections
on the Startup Page. Enter in the scaling for the transmitter connected to the analog
input. Min. input is the zero scale temperature of the transmitter (i.e. 1 Volt or 4 mA).
Max. input is the full scale temperature of the transmitter (i.e. 5 Volts or 20 mA).
Fixed temperature: Enabled if Fixed was selected for Temperature for meter correc-
tions on the Startup Page. Enter an average temperature of the process fluid.
Temperature alarm
Enter the low and high alarm limits. A temperature reading outside of these limits causes a
Temperature Validity alarm.
Pressure
Is pressure gage or absolute
Select either Gage or Absolute for the type of pressure reading desired. If a live
pressure transmitter is connected, select the type of reading the transmitter
outputs. If Absolute is selected, you must also enter the Atmospheric pressure.
Live pressure
Enabled if Live was selected for Pressure for meter corrections on the Startup Page.
Enter in the scaling for the transmitter connected to the analog input. Min. input is
the zero scale pressure of the transmitter (i.e. 1 Volt or 4 mA). Max. input is the full
scale pressure of the transmitter (i.e. 5 Volts or 20 mA).
Fixed pressure
Enabled if Fixed was selected for Pressure for meter corrections on the Startup Page.
Enter an average pressure of the process fluid.
Pressure alarm
Enter the low and high alarm limits. A pressure reading outside of these limits causes
a Pressure Validity alarm.
Table 5-11 Daniel MeterLink Field Setup Wizard
Page Description