Reference, Installation, and Operations Manual Section 5: Startup and meter configuration
3-9000-743 Rev S June 2013
Current Outputs Page 141
Table 5-15 Data Points for Analog (Current) Output Configuration
Daniel MeterLink
Display Name
Data Points, Options and Guidelines
Content:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
• AO1Content
• AO2Content
Options:
• Uncorrected (Actual) flow rate (0)
• Standard (corrected) flow rate (1)
• Average flow velocity (2)
• Average sound velocity (3)
• Energy rate (4)
• Mass rate (5)
Guidelines:
• For options and guidelines, see Section 6.2.1 and Daniel
MeterLink online help.
Direction:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
• AO1Dir
• AO2Dir
Options:
• Reverse (0)
• Forward (1)
• Absolute (2)
Guidelines:
• For options and guidelines, see Section 6.2.1 and Daniel
MeterLink online help.
Full scale volumetric flow rate:
Series 100 Option Board
Series 100 Plus Option Board
(if installed)
Data points affected:
• AO1FullScaleVolFlowRate
• AO2FullScaleVolFlowRate
Options:
• Enter a flow rate value (m
3
/hour or ft
3
/hour)
Guidelines:
• This point is only used when the current (analog) output content is
either the actual (uncorrected) or standard (corrected) flow rate.
• This point specifies the volumetric flow rate associated with the
maximum current (20 mA).
• For options and guidelines, see Section 6.2.1 and Daniel
MeterLink online help.