Carrier 17EX Air Conditioner User Manual


 
Table 12 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
PRESTART ALERT STARTS LIMIT EXCEEDED STARTS EXCESSIVE Compressor Starts (8 in
12 hours)
Depressthe RESETsoftkeyifadditional startis
required. Reassess start-up requirements.
PRESTART ALERT HIGH MOTOR TEMPERATURE MTRW [VALUE] exceeded limit of [LIMIT]*.
Check motor temperature.
Check motor cooling line for proper operation.
Check for excessive starts within a short time
span.
PRESTART ALERT HIGH BEARING TEMPERATURE MTRB [VALUE] exceeded limit of [LIMIT]*.
Check thrust bearing temperature.
Checkoil heaterfor properoperation, checkfor
low oil level, partially closed oil supply valves,
etc. Check sensor accuracy.
PRESTART ALERT HIGH DISCHARGE TEMP CMPD [VALUE] exceeded limit of [LIMIT]*.
Check discharge temperature.
Check sensor accuracy. Allow discharge tem-
perature to cool. Check for excessive starts.
PRESTART ALERT LOW REFRIGERANT TEMP ERT [VALUE] exceeded limit of [LIMIT]*. Check
refrigerant temperature.
Checktransduceraccuracy.Checkforlowchilled
water/brine supply temperature.
PRESTART ALERT LOW OIL TEMPERATURE OILT [VALUE] exceeded limit of [LIMIT]*.
Check oil temperature.
Check oil heater power, oil heater relay.Check
oil level.
PRESTART ALERT LOW LINE VOLTAGE V P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
Checkvoltagesupply.Checkvoltagetransform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 Table.
PRESTART ALERT HIGH LINE VOLTAGE V P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
Checkvoltagesupply.Checkvoltagetransform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 table.
PRESTART ALERT HIGH CONDENSER PRESSURE CRP [VALUE] exceeded limit of [LIMIT]*. Check
condenser water and transducer.
Check for high condenser water temperature.
Check transducer accuracy.
PRESTART ALERT HIGH GEAR OIL TEMP GEAOILT [VALUE] exceeded limit of [LIMIT].*
Check gear oil cooler flow.
Check for cooler water flow. Check sensor for
accuracy.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
E. NORMAL OR AUTO.-RESTART
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
STARTUP IN PROGRESS OCCUPIED MODE Chiller starting. Time schedule is occupied.
STARTUP IN PROGRESS REMOTE CONTACT CLOSED Chiller starting. Remote contacts are closed.
STARTUP IN PROGRESS START COMMAND IN EFFECT
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
AUTORESTART IN PROGRESS OCCUPIED MODE Chiller starting. Time schedule is occupied.
AUTORESTART IN PROGRESS REMOTE CONTACT CLOSED Chiller starting. Remote contacts are closed.
AUTORESTART IN PROGRESS START COMMAND IN EFFECT
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
F. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
SPARE SENSOR ALERT COMMON CHWS SENSOR Sensor Fault:Checkcommon CHWSsensor.
Check alert temperature set points on EQUIP-
MENT SERVICE table, SERVICE2 screen.
Check sensor for accuracy if reading is not
accurate.
SPARE SENSOR ALERT COMMON CHWR SENSOR Sensor Fault: Check common CHWR
sensor.
SPARE SENSOR ALERT REMOTE RESET SENSOR Sensor Fault: Check remote reset tempera-
ture sensor.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 1 Sensor Fault: Check temperature sensor
Spare 1.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 2 Sensor Fault: Check temperature sensor
Spare 2.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 3 Sensor Fault: Check temperature sensor
Spare 3.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 4 Sensor Fault: Check temperature sensor
Spare 4.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 5 Sensor Fault: Check temperature sensor
Spare 5.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 6 Sensor Fault: Check temperature sensor
Spare 6.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 7 Sensor Fault: Check temperature sensor
Spare 7.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 8 Sensor Fault: Check temperature sensor
Spare 8.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 9 Sensor Fault: Check temperature sensor
Spare 9.
87