Carrier 17EX Air Conditioner User Manual


 
Table 2 LID Display Data (cont)
EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
.
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT
.
LEAD/LAG CONFIGURATION SCREEN
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
0-3 leadlag 0
Load Balance Option DISABLE/ENABLE loadbal DISABLE
Common Sensor Option DISABLE/ENABLE commsens DISABLE
LAG Percent Capacity 25-75 % lag per
50
LAG Address 1-236 lag add
92
LAG START Timer 2-60 MIN lagstart 10
LAG STOP Timer 2-60 MIN lagstop 10
PRESTART FAULT Timer 0-30 MIN preflt 5
STANDBY Chiller Option DISABLE/ENABLE stndopt DISABLE
STANDBY Percent Capacity 25-75 % stnd per
50
STANDBY Address 1-236 stnd add
93
27