Carrier 17EX Air Conditioner User Manual


 
Table 21 Marine Waterbox Cover Weights*
HEAT EXCHANGER
SIZE
DESIGN MAXIMUM WATER PRESSURE COOLER CONDENSER
psi kPa lb kg lb kg
45-48
150 1034 2236 1015 1275 579
300 2068 3060 1389 1660 754
55-57
150 1034 1643 746
300 2068 2243 1018
*Heat exchangers with marine waterboxes have heavier dry and operating weights than heat exchangers
with nozzle-in-head waterboxes.
Table 22 NIH Waterbox Cover Weights*
HEAT EXCHANGER
SIZE
PASSES
DESIGN MAXIMUM WATER PRESSURE COOLER CONDENSER
psi kPa lb kg lb kg
45-48
1
150 1034 2997 1361 1735 788
300 2068 4225 1918 2510 1140
2†
150 1034 2984 1355 1885 856
300 2068 4188 1901 2590 1176
3
150 1034 3035 1378 1777 807
300 2068 4244 1927 2539 1153
55-57
1
150 1034 2032 923
300 2068 2940 1335
2†
150 1034 2649 1203
300 2068 3640 1653
3
150 1034
300 2068
NIH Nozzle-in-Head
*The 150 psig (1034 kPa) waterbox cover weights are included in the dry weight shown in Table 15.
†Two different waterbox covers are present on 2-pass chillers. The weight shown in this table represents the
weight of the waterbox cover that contains the nozzles. A blank waterbox cover is also present on 2-pass
units. The weight of the blank waterbox cover is identical to the weight of the same size marine waterbox
cover. Refer to Table 21.
Table 23 Approximate Refrigerant (HCFC-134a) Charge*
COOLER
SIZE
CONDENSER
SIZE
TOTAL CHILLER
CHARGE
lb kg
45
45
4100 186046
47
55
4320 196056
57
46
45
4200 190546
47
55
4420 200556
57
47
45
4300 195046
47
55
4520 205056
57
48
45
4580 207746
47
55
4800 217756
57
*Total chiller refrigerant charge includes the cooler, condenser, and economizer charges.
NOTE: Regulations mandate that chiller shipping charge is limited to 7500 lb (3402 kg).
103