Carrier 17EX Air Conditioner User Manual


 
Table 2 LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
.
5. Scroll down to highlight CONFIG.
6. Press SELECT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA –30-30 (–17-17) DEG F (DEG C) deg 20ma
10(6)
RESET TYPE 2
Remote Temp (No Reset) –40-245 (–40-118) DEG F (DEG C) res rt1
85 (29)
Remote Temp (Full Reset) –40-245 (–40-118) DEG F (DEG C) res rt2 65 (18)
Degrees Reset –30-30 (–17-17) DEG F (DEG C) res rt 10(6)
RESET TYPE 3
CHW Delta T (No Reset) 0-15 (0-8) DEG F (DEG C) restd 1
10(6)
CHW Delta T (Full Reset) 0-15 (0-8) DEG F (DEG C) restd 2 0(0)
Degrees Reset –30-30 (–17-17) DEG F (DEG C) deg chw 5(3)
Select/Enable Reset Type 0-3 res sel
0
ECW CONTROL OPTION DISABLE/ENABLE ecw opt
DISABLE
Demand Limit At 20 mA 40-100 % dem 20ma 40
20 mA Demand Limit Option DISABLE/ENABLE dem sel DISABLE
Auto Restart Option DISABLE/ENABLE astart DISABLE
Remote Contacts Option DISABLE/ENABLE r contact
DISABLE
Temp Pulldown Deg/Min 2-10 tmp ramp
3
Load Pulldown %/Min 5-20 kw ramp 10
Select Ramp Type: 0/1 ramp opt 1
Temp=0,Load=1
Loadshed Group Number 0-99 ldsgrp 0
Loadshed Demand Delta 0-60 % ldsdelta 20
Maximum Loadshed Time 0-120 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number 3-99 occpcxxe 3
Broadcast Option DISABLE/ENABLE occbrcst DISABLE
ICE BUILD Option DISABLE/ENABLE ibopt DISABLE
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both 0-2 ibterm 0
ICE BUILD Recycle Option DISABLE/ENABLE ibrecyc DISABLE
NOTE: = delta degrees.
26