Table 2 — LID Display Data (cont)
EXAMPLE4—STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS04.
4. Press SELECT
.
DESCRIPTION RANGE UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
Main Gear Oil Pump OFF/ON MAINPMP1
Auxiliary Gear Oil Pump OFF/ON AUXPMP2
Gear Oil Pressure −6.7 to 420 (−46 to 2896) psi (kPa) GEAROILP
Gear Oil Temperature −40 to 245 (−40 to 118) DEG F (DEG C) GEAROILT
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SETPOINT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Base Demand Limit 40-100 % DLM 100
LCW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) lcw sp
50.0 (10.0)
ECW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) ecw sp 60.0 (15.6)
ICE BUILD Setpoint 20- 60 (–6.7-15.6) DEG F (DEG C) ice sp
40.0 ( 4.4)
25