Emerson Process Management Rosemount 2410 Water Heater User Manual


 
Reference Manual
300530EN, Rev BA
September 2012
6-25
Rosemount 2410
Section 6. Service and Troubleshooting
Map conflict tank no. Input register no. 6260
Check that tank measurement variables
are mapped to the right source
parameters (In TankMaster Winsetup,
right-click the ATD device icon associated
with the current tank, and click the
Properties option. In the 22XX ATD
window select the Advanced Parameter
Source Configuration tab.)
Contact Emerson Process
Management/Rosemount TankGauging
service department.
Map conflict TMV type
(TMV=Tank Measurement Variable)
Input register no. 6262
0: TMV Level
1: TMV Ullage
2: TMV Level Rate
3: TMV Signal Strength
4: TMV Free Water Level
5: TMV Vapor Pressure
6: TMV Liquid Pressure
7: TMV Air Pressure
8: TMV Ambient Temperature
9: TMV Vapor Avg Temperature
10: TMV Liquid Avg Temperature
11: TMV Tank Avg Temperature
12-27: TMV Temp1 - TMV Temp 16
50: TMV Observed Density
51: TMV Reference Density
52: TMV Flow Rate
53: TMV Tank Volume
54: TMV Tank Height
55: TMV Middle Pressure
56: TMV Delta Level
60-64: TMV USER DEF 1 - 5
Map conflict device 1 Input register no. 6264
Map conflict device 1 TV no.
(TV=Tank Variable)
Input register no. 6266
TV number 0 - 1019 (Level, Ullage, Level
Rate, Signal Strength etc.)
Map conflict device 2 Input register no. 6268
Map conflict device 2 TV no.
(TV=Tank Variable)
Input register no. 6270
TV number 0 - 1019 (Level, Ullage, Level
Rate, Signal Strength etc.)
Internal map conflict Input register no. 6272
Bit 1: TMV Vapor average temperature
Bit 2: TMV Liquid average temperature
Bit 3: TMV Tank average temperature
Bit 4: TMV Observed Density
Bit 5: TMV Reference Density
Bit 6: TMV Tank Volume
Bit 7: Mult TV Map
Bit 8: TMV Internal Map
Bit 9: TMV Arithmetic Value
Message Description Action