Section 3. Installation
Figure 3-8 illustrates an example with a 2-in-1 version of the 5900S in a SIL
safety installation. A 4-wire cable is used to connect the Primary and
Secondary Tankbuses through the same cable entry. The SIL alarm wire is
connected through a separate cable entry. A junction box is used to provide
sufficient number of connections for the field devices to the Primary and
Secondary Tankbus.
Figure 3-8. Raptor SIL system
with a 5900S connected to
separate Tank buses
5900S Radar
Level Gauge
2240S Multi-input
Temperature
Transmitter
Junction box
2230 Display
Pressure
transmitter
Pressure
transmitter
Terminators for Primary and
Secondary Tankbus
Primary 2410 Tank Hub
4-wire cable for connection of
Primary Tankbus and Secondary
Tankbus to 2-in-1 5900S
Primary Tank Hub is
connected to the
electronic unit of the
5900S 2-in-1 level
gauge which is used
for SIL overfill alarm
Secondary 2410 Tank Hub
Primary Tankbus Secondary Tankbus
2230 Display
Secondary Tank Hub
is connected to the
5900S electronic unit
used for level
measurements