Section 3. Installation
Conductor Recommendations
Ensure that you use cables suitable for the terminal block of the 2410. The
terminal block is designed for cables that meet the specifications as illustrated
below.
Figure 3-15. Conductor and
insulation requirements
Table 3-7. Conductor
cross-sectional area
Stripping length: 10 mm
Conductor cross-sectional area,
see Table 3-7
Conductor connection Cross-section (mm
2
)
Minimum Maximum
Solid 0.5 4
Flexible 0.5 2.5
Flexible, ferrule with plastic
collar
0.5 1.5