Reference Manual
300530EN, Rev BA
September 2012
6-7
Rosemount 2410
Section 6. Service and Troubleshooting
6.2.6 Diagnostics TankMaster WinSetup offers the option to view diagnostic registers for the
Rosemount 2410 Tank Hub. The diagnostic registers are selected from
available Input and Holding Registers to provide a quick overview of the
current device status. For a more comprehensive troubleshooting you may
use the View Input Registers function (see also section “Viewing Input and
Holding Registers” on page 6-2).
To view and configure the diagnostic registers:
1. In the TankMaster WinSetup workspace select the 2410 Tank Hub icon.
2. Click the right mouse button and choose View Diagnostic Registers.
The register values in the View Diagnostic Registers window are of read only
type. They are loaded from the device as the window is opened.
A grey background color of a table cell in the Value column means that the
register is of either Bitfield or ENUM type. By double-clicking the cell, an
Expanded Bitfield/ENUM window can be opened for this type of register.
If needed, the values can be presented as hexadecimal numbers. This
applies to registers of the Bitfield and ENUM types. Select the Show in Hex
check box to present Bitfield and ENUM registers as hexadecimal numbers.
The Configure button lets you open the Configure Diagnostic Registers
window, allowing you to change the list of registers to be displayed in the View
Diagnostic Registers window.
The Configure Diagnostic Registers window also has a Log Setup button for
access to the Register Log Scheduling window which allows you to setup a
log schedule for automatic start and stop of register logging. See “Logging
Measurement Data” on page 6-17 for more information
See the Raptor System Configuration Manual (Document No. 300510EN) for
more information on the View Diagnostic Registers function.