Emerson Process Management Rosemount 2410 Water Heater User Manual


 
Reference Manual
300530EN, Rev BA
September 2012
3-29
Rosemount 2410
Section 3. Installation
3.4.13 Intrinsically Safe
Terminal Block
The Intrinsically safe side of the Rosemount 2410 Tank Hub connects to the
Tankbus which communicates with field devices on the tank.
Figure 3-20. Intrinsically safe
terminal block
Table 3-11. Terminal
assignment for intrinsically safe
side
Tankbus
The devices on the tank communicates with the Rosemount 2410 via the
intrinsically safe Tankbus. All field devices in the Raptor system have built-in
communication modems for FISCO F
OUNDATION fieldbus (FF) communication
and will automatically communicate with the 2410 when connected to the
Tankbus.
Optional Secondary Bus
In addition to the Tankbus an optional intrinsically safe bus is available for
communication with devices not compatible with F
OUNDATION fieldbus. It
allows you to connect devices for intrinsically safe HART 4-20 mA analog
input/output communication.
Ground screws
X2
IS/Exi
Terminal Designation Function
1a FB + Intrinsically Safe Tankbus positive (+) terminal
1b FB + Intrinsically Safe Tankbus positive (+) terminal
2a FB - Intrinsically Safe Tankbus negative (-) terminal
2b FB - Intrinsically Safe Tankbus negative (-) terminal
3 IS I/O+ IS Input/Output + HART / 4-20 mA (Secondary Bus)
4 IS I/O - IS Input/Output - HART / 4-20 mA (Secondary Bus)
5W3
Not used (future option)
6 W4
GND_1 GND_1 Housing chassis/Tankbus shield
GND_2 GND_2 Housing chassis/Tankbus shield