Reference Manual
300530EN, Rev BA
September 2012
6-9
Rosemount 2410
Section 6. Service and Troubleshooting
c. From the Available Devices pane choose a 2410 Tank Hub to be
programmed and click the Move button.
d. Repeat for each device to be programmed.
Use the Remove button if you want to change the list of devices to
be programmed.
7. Click the Browse button to locate the flash program file. A flash file is
identified by file extension *.cry.
For a 2410 Tank Hub, a flash file name may typically look like:
2410_APPL_xxx_yy.cry, where “x” and “y” indicate software version.
8. In the Program Devices window click the Start Programming button.
Now the Start Device Programming window appears:
9. Click the Start Programming button to activate device programming.
10. Programming may take up to two hours for a 2410 Tank Hub connected
to a TankMaster PC via a 2160 Field Communication Unit. The
programming procedure will continue with one device after the other until
all Tank Hubs selected in the Program Devices window are upgraded.
By connecting a 2410 directly to a host computer, and using the RS485
Modbus protocol at a maximum baudrate of 38400, programming time
may be reduced to 5 to 10 minutes (see “Primary Bus” on page C-4 for
information on how to configure the Primary Bus).
11. The 2410 operates as normal during the reprogramming procedure.
Once programming is finished, the 2410 will automatically perform a
restart indicated by “WAIT” on the integral display for a couple of
minutes.