Emerson Process Management Rosemount 2410 Water Heater User Manual


 
Reference Manual
300530EN, Rev BA
September 2012
6-21
Rosemount 2410
Section 6. Service and Troubleshooting
Incorrect level reading from radar
level gauge
Configuration error
Check configuration of the level gauge; in TankMaster
Winsetup open Properties for the level gauge
associated with the tank.
See the Rosemount 5900S Reference Manual
(Document no. 300520en) and the Raptor System
Configuration Manual (Document no. 300510EN) for
more information on how to configure a Rosemount
5900S Radar Level Gauge.
Measurement units are not compatible
with host system
If default database is loaded to the 2410 Tank Hub, do one
of the following:
in TankMaster WinSetup verify system units and
re-install the tank associated with the 2410 Tank Hub
update Holding Registers with correct measurement
units
Hardware failure
Check diagnostics information, see “Diagnostics” on
page 6-7.
Contact Emerson Process Management/Rosemount
TankGauging service department.
No output on the 2410 integral
display
Hardware failure
Check the model code to verify that the 2410 was
ordered with the LCD display option.
Check display connection.
Check diagnostics information, see “Diagnostics” on
page 6-7.
Contact Emerson Process Management/Rosemount
TankGauging service department.
The Error LED (red) is blinking Various reasons such as hardware or
software failure, communication, or
configuration error
See “Error Messages” on page 5-5 and “Error
Messages” on page 6-26.
Check Device Status input register (see “Device Status”
on page 6-23).
The Status LED (yellow) is
blinking
Normal operation. The yellow Status LED
blinks at a constant rate of one flash every
other second.
See “LED” on page 5-6 for more information.
Configuration can not be saved Write protection switch is set to the ON
position
Check write protection switch on the display, see “Write
Protection Switch” on page 6-11.
The 2410 is write protected in TankMaster
WinSetup
Check write protection in TankMaster WinSetup, see
“Write Protection” on page 6-10.
Application software installed which is
incompatible with current holding register
setup
Reset holding registers to the default database setting,
see “Loading the Default Database” on page 6-16 and
restart the 2410 Tank Hub.
Corrupt holding registers
Reset holding registers to the default database setting,
see “Loading the Default Database” on page 6-16 and
restart the 2410 Tank Hub.
Symptom Possible cause Action