Section 2 Overview
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
2.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-5
2.3 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-6
2.4 Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . page 2-12
2.1 INTRODUCTION The Rosemount 2410 Tank Hub collects measurement data and status
information from field devices designed for the Rosemount Raptor system via
the intrinsically safe 2-wire Tankbus
(1)
. The Tankbus carries both data
transmission and power supply (see also “Tankbus” on page 3-8).
The Rosemount 2410 is designed for use in hazardous area Zone 1 (Class 1,
Division 1) and communicates with field devices in Zone 1 via the intrinsically
safe Tankbus.
The 2410 is available in two versions for single tanks or multiple tanks. The
multiple tanks version supports up to 10 tanks and 16 devices.
Measurement data and status information from one or more tanks is
distributed via the Primary Bus to a Rosemount 2160 Field Communication
Unit (FCU). Data is buffered by the 2160 and distributed to a TankMaster PC,
or a host system, whenever the FCU receives a request for data. In case no
FCU is included in the system, the 2410 can communicate directly with a host
computer.
Figure 2-1. System integration
(1) The intrinsically safe Tankbus complies with the FISCO FOUNDATION™ fieldbus standard.
TankMaster
2410 Tank Hub
Modem
FCU 2160 Field
Communication Unit
Relay Outputs
Secondary Bus
(Non-IS)
Primary Bus
Tankbus
2240S Temperature
Transmitter
2230 Display
Group Bus
Zone 1
Zone 0
5900S Radar
Level Gauge
Secondary bus (IS)