Section 6. Service and Troubleshooting
No communication with one or
more devices on the Tankbus
Wiring
Check that the devices appear in the Device Live List
(see “Device Live List” on page 6-4).
Check diagnostics information, see “Diagnostics” on
page 6-7 for warning or error messages.
Check that wires are properly connected to the
terminals.
Check for dirty or defective terminals.
Check wire insulation for possible short circuits to
ground.
Check diagnostics information (see “Diagnostics” on
page 6-7) for information that indicate bad
communication on the Tankbus:
- Input registers 1300 to 1328 provide general
information on Tankbus communication
- Input registers 1330 to 1648 provide information on
specific devices on the Tankbus.
Check diagnostics information (see “Diagnostics” on
page 6-7) for possible hardware faults that indicate
short circuits or ground faults:
- check Input Register 1326 for short circuits
- check Input Register 1328 for ground faults.
Check that there are no multiple shield grounding points
Check that the cable shield is grounded at the power
supply end (2410 Tank Hub) only.
Check that the cable shield is continuous throughout
the Tankbus network.
Check that the shield inside the instrument housing
does not come into contact with the housing.
Check that there is no water in conduits.
Check for proper polarity at the terminals (Rosemount
5300 and 5400).
Use shielded twisted pair wiring.
Connect wiring with drip loops.
Check the loop impedance.
Incorrect Tankbus termination
Check that there are two terminators on the Tankbus
(see section “Tankbus” on page 3-8).
Check that terminations are placed at both ends of the
Tankbus.
Check that the built-in termination in the 2410 Tank Hub
is enabled.
Too many devices on the Tankbus
Check that the total current consumption of the devices
on the Tankbus is less than 250 mA, see “Power
Budget” on page 3-7.
Remove one or more devices from the Tankbus. The
2410 Tank Hub supports a single tank. The multiple
tank version of the 2410 supports up to 10 tanks.
Cables are too long
Check that the input voltage on the device terminals is
9 V or more (see section “Tankbus” on page 3-8).
Software or hardware failure
Check diagnostics information, see “Diagnostics” on
page 6-7.
Check Device Status input register, see “Device Status”
on page 6-23.
Contact Emerson Process Management/Rosemount
TankGauging service department.
Symptom Possible cause Action