Section 4. Configuration
4.6.3 FCU 2160
Configuration
In case the system includes a 2160 Field Communication Unit (FCU), it has to
be installed prior to installing the Rosemount 2410 Tank Hub. The following is
a brief description of how to install a 2160 FCU. See the Raptor System
Configuration Manual (Document no. 300510EN) for a more comprehensive
description.
To install and configure a 2160 FCU:
1. Start the installation wizard in TankMaster WinSetup and choose Device
Type=FCU 2160.
2. Enable communication with the TankMaster PC:
Select communication channel
Set the communication address
3. Configure the FCU: specify Port type (Field Bus/Group Bus), Baud rate,
Data bits, Stop bits, and Parity.
4. Configure the Slave Database.
Set Slave Type=2410_Level in the first free position of the Slave Type
column.
A 2410_Temp device is automatically added to the Slave Database.
Ensure that the Modbus Addresses of the connected devices are
properly set. These addresses must correspond to the 2410 Tank Hub
database settings (see “Basic Configuration of a Rosemount 2410” on
page 4-3 for more information).
Figure 4-2. The Slave Database
has to be configured for level
gauges and temperature
transmitters
2410_Level
2410_Temp is
automatically added