Emerson Process Management Rosemount 2410 Water Heater User Manual


 
Reference Manual
300530EN, Rev BA
September 2012
Rosemount 2410
6-14
Section 6. Service and Troubleshooting
6.2.11 Testing the
Relays
The Manual Control of Relay function lets you manually open or close the
Rosemount 2410 Tank Hub built-in relays in order to verify the relay function.
After the specified Safety Reset Time the relay automatically returns to normal
mode.
To change relay state by using the TankMaster WinSetup program do the
following:
1. In the TankMaster WinSetup workspace select the 2410 icon.
2. Click the right mouse button and choose Manual Control Relay.
Table 6-2. Manual control of
relay function
3. Select the virtual relay functions to be tested; Virtual Relay 1,
Virtual Relay 2, etc.
Up to ten virtual relay functions can be configured for a 2410 Tank Hub.
See “Advanced Configuration in Winsetup” on page C-3 and “Relay
Output” on page C-6 for more information.
4. Specify a Safety Reset Time. This value specifies the time period for the
relay to stay in the test state. When the specified period of time has
elapsed, the relay automatically returns to the original state. The relay
will reset even if communication with the TankMaster PC would fail.
5. Choose the desired Manual Relay State. Available options are Alarm,
Normal, and Toggle.
6. Click the Set button. Now the selected relay changes state for the
specified number of seconds and then returns to the previous state.