Reference Manual
300530EN, Rev BA
September 2012
6-23
Rosemount 2410
Section 6. Service and Troubleshooting
6.3.1 Device Status The current device status is shown in Input Register 1000. You can view the
device status register by opening the Diagnostic window (see “Diagnostics”
on page 6-7) or the View Input Registers window (see “Viewing Input and
Holding Registers” on page 6-2).
Double-clicking the Value field of the Device Status register opens an
expanded bitfield window with informaion on the current device status as
shown in Figure 6-7.
Figure 6-7. Input Register
Device Status
Table 6-4. Device status
messages
Double-click the Value field to open
the Expanded Bitfield window
Message Bit no. Description Action
Device Warning 1 A device warning is active. See “Warning Messages” on page 6-24
for details.
Device Error 7 A device error is active. See “Error Messages” on page 6-26 for
details.
Simulation Mode Active 8 Simulation mode active. Stop Simulation mode.
Write Protected 18 The device is write protected with a switch
or in the TankMaster WinSetup program.
Check the write protection switch, see
“Write Protection Switch” on page 6-11.
Check write protection state in
TankMaster WinSetup, see “Write
Protection” on page 6-10.