Emerson Process Management Rosemount 2410 Water Heater User Manual


 
Reference Manual
300530EN, Rev BA
September 2012
Rosemount 2410
6-24
Section 6. Service and Troubleshooting
6.3.2 Warning
Messages
Warning messages are displayed in the Rosemount Tankmaster program.
Input Register 1004 provides an overview of active device warnings (see
“Diagnostics” on page 6-7 or “Viewing Input and Holding Registers” on
page 6-2 for information on how to view diagnostics and various Input
registers in TankMaster WinSetup).
For each warning message that may appear in Input register 1004, detailed
information can be found in Input registers 6200 to 6248 as shown in
Table 6-5.
Table 6-5. Warning message
descriptions
Message Description Action
RAM warning Input register no. 6200.
Contact Emerson Process
Management/Rosemount TankGauging
service department.
FPROM warning Input register no. 6204.
Hreg warning Input register no. 6208.
SW warning Input register no. 6212.
Other memory warning Input register no. 6216.
Bit 1: Stack
System warning Input register no. 6220.
Display warning Input register no. 6224.
Bit 0: Communication
Bit 1: Configuration
Aux warning Input register no. 6228.
Bit 0: Internal temperature
Bit 1: Power
FF stack warning Input register no. 6232.
Tankbus communication warning Input register no. 6236.
Bit 0: Device restarted
Bit 1: Device open failed
Bit 2: Device address changed
Bit 3: Live List no free position
Bit 4: Port changed
Bit 5: Exceeded FF number of retries
Bit 6: Power failure
Bit 7: Ground failure
Host communication warning Input register no. 6240.
Bit 0: Multiple configuration
Bit 1: Primary bus configuration
Bit 2: Secondary bus configuration
Data Manager warning Input register no. 6244.
Bit 0: Frozen data
Bit 1: TMV mapping
Configuration warning Input register no. 6248.
Bit 0: Invalid strapping table
Bit 1: Tank configuration
Bit 11: Model Code invalid string
Bit 12: Model Code invalid code