Section 6. Service and Troubleshooting
6.2.13 Loading the
Default Database
The various configuration parameters of the 2410 Tank Hub is stored in a
Holding Register database. The Holding Register factory setting is stored
in the default database. TankMaster WinSetup offers the option to load the
default database. This may be useful if, for example, you would like to try out
new database settings and then be able to reload the original factory settings.
In case error messages appear or other problems occur concerning the
database, troubleshooting the cause of these problems is recommended
before loading the default database.
It is recommended that the current database is backed up before the Default
Database is loaded. See “Configuration Backup” on page 6-5 for information
on how to save the current database.
NOTE!
The communication adress of the device remains unaltered when the default
database is loaded.
NOTE!
When the default database is loaded to the 2410 Tank Hub measurement
units are reset to Metric Units.
To load the default database:
1. Select the desired device icon in the TankMaster WinSetup workspace
window.
2. Click the right mouse button and choose the View Holding Register
option.
3. Choose the All option and type 65510 in the Start Register input field.
Type the desired number of registers to be displayed in the Number of
Registers field and click the Read button.
4. Type 65510 in the Value input field.
5. Click the Apply button to load the default database.
6. Finish by clicking the Close button.
7. Verify that measurement units are compatible with the current host
system configuration.