Section 6. Service and Troubleshooting
2410 icon in TankMaster
WinSetup is red
Simulation mode active
Stop simulation mode; open WinSetup Set Simulation
Mode window and click the Stop button.
All measurement values are
indicated with “SensFail” in the
WinSetup Tank View window, and
with “Error” in the WinOpi Tank
View window.
Map conflict. One or more tank
measurement variables are mapped to
the wrong source parameter. For
example: Vapor Temperature is mapped
to Manual Value.
Check diagnostics information (see “Diagnostics” on
page 6-7) for possible Device Warning messages:
- in case there is a “Data Manager” warning, check
Input Register 6244
- if register 6244 indicates a “TMV Mapping” warning
check Input Registers 6260 to 6270 for tank
measurement variable mapping conflicts
In TankMaster Winsetup, right-click the ATD device icon
associated with the current tank, and click the
Properties option. In the 22XX ATD window select the
Advanced Parameter Source Configuration tab. Check
that tank measurement variables are mapped to the
right source parameters.
Symptom Possible cause Action