Carrier 30RAP010-060 Air Conditioner User Manual


 
99
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — RUNTEST
DESCRIPTION VALUE UNITS POINT NAME
Percent Total Capacity nnn % CAPA_T
Percent Available Cap. nnn % CAPA_A
Discharge Pressure nnn.n psig DP_A
Suction Pressure nnn.n psig SP_A
Head Setpoint nnn.n FHSP
Saturated Condensing Tmp nnn.n FTMP_SCTA
Saturated Suction Temp nnn.n FTMP_SSTA
Compr Return Gas Temp nnn.n FTMP_RGTA
Discharge Gas Temp nnn.n FDISGAS
Suction Superheat Temp nnn.n ^F SH_A
Compressor A1 Relay On/Off K_A1_RLY
Compressor A2 Relay On/Off K_A2_RLY
Minimum Load Valve Relay On/Off MLV_RLY
Compressor A1 Feedback On/Off K_A1_FBK
Compressor A2 Feedback On/Off K_A2_FBK
Percent Total Capacity nnn % CAPB_T
Percent Available Cap. nnn % CAPB_A
Discharge Pressure nnn.n psig DP_B
Suction Pressure nnn.n psig SP_B
Head Setpoint nnn.n FHSP
Saturated Condensing Tmp nnn.n FTMP_SCTB
Saturated Suction Temp nnn.n FTMP_SSTB
Compr Return Gas Temp nnn.n FTMP_RGTB
Suction Superheat Temp nnn.n ^F SH_B
Compressor B1 Relay On/Off K_B1_RLY
Compressor B2 Relay On/Off K_B2_RLY
Minimum Load Valve Relay On/Off MLV_RLY
Compressor B1 Feedback On/Off K_B1_FBK
Compressor B2 Feedback On/Off K_B2_FBK
Fan 1 Relay On/Off FAN_1
Fan 2 Relay On/Off FAN_2
Outside Air Temperature nnn.n FOAT
Space Temperature nnn.n F SPT
Cooler Pump Relay 1 On/Off COOLPMP1
Cooler Pump Relay 2 On/Off COOLPMP2
Cooler Pump 1 Interlock Open/Closed PMP1_FBK
Cooler Pump 2 Interlock Open/Closed PMP2_FBK
Cooler Entering Fluid nnn.n F COOL_EWT
Cooler Leaving Fluid nnn.n F COOL_LWT
Compressor A1 Size nnn tons SIZE_A1
Compressor A2 Size nnn tons SIZE_A2
Compressor B1 Size nnn tons SIZE_B1
Compressor B2 Size nnn tons SIZE_B2
Cooler Flow Switch On/Off COOLFLOW