Table 10 — Configuration Mode and Sub-Mode Directory (cont)
* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
EXV.A CIR A EXV CONFIGURATION
STR.A XXX EXV CIRC.A START POS Range: 0 - 100 Default: 30
MIN.A XXX EXV CIRC.A MIN POSITION Range: 0 - 100 Default: 8
RNG.A XXXXX EXVA STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.A XXXXX EXVA STEPS PER SECOND Range: 0 - 65535 Default: 200
POF.A XXX EXVA FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.A XXXXX EXVA MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.A XXXXX EXVA MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR.A XXX EXVA OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.A 0,1 EXVA STEPPER TYPE
0 = UNIPOLAR
1 = BIPOLAR Default: 1
H.SCT XXX HIGH SCT THRESHOLD Range: 50 - 140 Default: 115
X.PCT XX OPEN EXV X% ON 2ND COMP Range: 0 - 30 Default: 10
X.PER XX MOVE EXV X% ON DISCRSOL Range: 0 - 30 Default: 5
A.PCT XXX PRE-OPEN EXV - FAN ADDING Range: 0 - 100 Default: 10
M.PCT XXX PRE-CLOSE EXV - FAN SUB Range: 0 - 100 Default: 10
S.PCT XXX PRE-CLOSE EXV - LAG SHUT Range: 0 - 100 Default: 10
DELY XXX LAG START DELAY Range: 0 - 100 Default: 10
EXV.B CIR B EXV CONFIGURATION
STR.B XXX EXV CIRC.B START POS Range: 0 - 100 Default: 50
MIN.B XXX EXV CIRC.B MIN POSITION Range: 0 - 100 Default: 8
RNG.B XXXXX EXVB STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.B XXXXX EXVB STEPS PER SECOND Range:
0 - 65535 Default: 200
POF.B XXX EXVB FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.B XXXXX EXVB MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.B XXXXX EXVB MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR.B XXX EXVB OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.B 0,1 EXVB STEPPER TYPE
0 = UNIPOLAR
1 = BIPOLAR Default: 1
MM MOTORMASTER CONFIGURATION
MMR.S YES/NO MOTORMASTER SELECT
P.GAN XX HEAD PRESSURE P GAIN Range: -20 - 20 Default: 1.0
I.GAN XX HEAD PRESSURE I GAIN Range: -20 - 20 Default: 0.1
D.GAN XX HEAD PRESSURE D GAIN Range: -20 - 20 Default: 0.0
MIN.S XXX MINIMUM FAN SPEED Range: 0 - 100 Default: 5.0
ENTER
ENTER