APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
OPT2
UNIT OPTIONS 2 CONTROLS
CTRL X Control Method
Default: 0
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = CCN Control
LOAD X Loading Sequence Select
Default: 1
1 = Equal
2 = Staged
LLCS X Lead/Lag Circuit Select
Default: 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT XX High LCW Alert Limit
Default: 60
Range: 2 to 60 F
DELY XX Minutes Off Time
Default: 0 Minutes
Range: 0 to 15 Minutes
ICE.M ENBL/DSBL Ice Mode Enable Default: Disable
LS.MD X Low Sound Mode Select Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
LS.ST 00:00 Low Sound Start Time Default: 00:00
LS.ND 00:00 Low Sound End Time Default: 00:00
LS.LT XXX % Low Sound Capacity Limit
Default: 100%
Range: 0 to 100%
CCN
CCN NETWORK CONFIGS
CCNA XXX CCN Address
Default: 1
Range: 0 to 239
CCNB XXX CCN Bus Number
Default: 1
Range: 0 to 239
BAUD X CCN Baud Rate
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
HP.A
HEAD PRESSURE CMP. DELTA
A1.DT XX SCT Delta For Comp A1
Default:12
Range: 0 to 50
A2.DT XX SCT Delta For Comp A2
Default:12
Range: 0 to 50
HP.B
HEAD PRESSURE CMP. DELTA
B1.DT XX SCT Delta For Comp B1
Default:12
Range: 0 to 50
B2.DT XX SCT Delta For Comp B2
Default:12
Range: 0 to 50