108
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Cooling Setpoint 2 CSP2 R/W °F 44.0 -20 - 70 AV:54 csp2_1
CSM Controlling Chiller MODE_1 R BV:30 mode_1_1
Demand Level 1 R % AV:75 dmv_lvl_1_perct_1
Demand Level 2 R % AV:76 dmv_lvl_2_perct_1
Demand Level 3 R % AV:77 dmv_lvl_3_perct_1
Demand Limit Switch 1 DMD_SW1 R BV:25 dmd_sw1_1
Demand Limit Switch 2 DMD_SW2 R BV:26 dmd_sw2_1
Demand/Sound Limited MODE_15 R BV:41 mode_15_1
Discharge Gas Temp DISGAS R °F AV:15 disgas_1
Discharge Pressure DP_A R psig AV:13 dp_a_1
Discharge Pressure DP_B R psig AV:23 dp_b_1
Dual Setpoint MODE_13 R BV:39 mode_13_1
Dual Setpoint Switch DUAL_IN R BV:29 dual_in_1
Element Comm Status R BV:2999 element_stat_1
Element Communications
Alarm
R BV:58 comm_lost_alm_1
Emergency Stop EMSTOP R/W Enabled Enabled/Emstop BV:6 emstop_1
Entering Fluid Temp EWT R °F AV:6 ewt_1
EXV % Open EXV_A R % AV:18 exv_a_1
EXV % Open EXV_B R % AV:27 exv_b_1
Fan 1 Relay FAN_1 R BV:22 fan_1_1
Fan 2 Relay FAN_2 R BV:23 fan_2_1
Head Setpoint HSP R °F AV:29 hsp_1
Heat Request HEAT_REQ R BV:28 heat_req_1
High SCT Circuit A MODE_21 R BV:47 mode_21_1
High SCT Circuit B MODE_22 R BV:48 mode_22_1
High Temperature Cooling MODE_18 R BV:44 mode_18_1
Ice Done ICE_DONE R BV:27 ice_done_1
Ice Setpoint CSP3 R/W °F 32.0 -20 - 32 AV:55 csp3_1
Lead/Lag Circuit Select LEAD_TYP R/W 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
AV:43 lead_typ_1
Lead/Lag Circuit Select LEAD_TYP R MSV:6 lead_typ_msv_1
Lead/Lag Leaving Fluid DUAL_LWT R °F AV:32 dual_lwt_1
Leadpump LEADPUMP R MSV:9 leadpump_msv_1
Leaving Fluid Temp - Prime
Variable
LWT R °F AV:7 lwt_1
Loading Sequence Select SEQ_TYPE R AV:74 seq_type_1
Local Schedule R BV:1 schedule_1
Low Cooler Suction Temp A MODE_7 R BV:35 mode_7_1
Low Cooler Suction Temp B MODE_8 R BV:36 mode_8_1
Low Sound Active LSACTIVE R BV:2 lsactive_1
Low Sound Mode MODE_25 R BV:51 mode_25_1
Low Temperature Cooling MODE_17 R BV:43 mode_17_1
Machine Operating Hours HR_MACH R hr AV:57 hr_mach_1
Machine Starts
CY_MACH R AV:58 cy_mach_1
Making ICE MODE_19 R BV:45 mode_19_1
Master/Slave Control MODE_3 R BV:32 mode_3_1
Minimum Comp. On Time MODE_23 R BV:49 mode_23_1
Minimum Load Valve Relay MLV_RLY R BV:15 mlv_rly_1
Minimum OFF Time Active MODE_10 R BV:38 mode_10_1
Minutes Off Time DELAY R/W min 0 0 - 15 AV:42 delay_1
Occupied OCC R BV:3 occ_1
Outside Air Temperature OAT R °F AV:34 oat_1
Override Modes in Effect MODE R BV:5 mode_1
Percent Available Cap. CAP_A R % AV:12 capa_a_1
Percent Available Cap. CAPB_A R % AV:22 capb_a_1
R—Read
W—Write