Table 5 — Temperature Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 7 — Set Points Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
UNIT ENT AND LEAVE UNIT TEMPS
CEWT XXX.X F COOLER ENTERING FLUID
CLWT XXX.X F COOLER LEAVING FLUID
OAT XXX.X F OUTSIDE AIR TEMPERATURE
SPT XXX.X F SPACE TEMPERATURE
DLWT XXX.X F LEAD/LAG LEAVING FLUID
CIR.A TEMPERATURES CIRCUIT A
SCT.A XXX.X F SATURATED CONDENSING TMP
SST.A XXX.X F SATURATED SUCTION TEMP
RGT.A XXX.X F COMPR RETURN GAS TEMP
D.GAS XXX.X F DISCHARGE GAS TEMP
SH.A XXX.X ^F SUCTION SUPERHEAT TEMP
CIR.B TEMPERATURES CIRCUIT B See Note
SCT.B XXX.X F SATURATED CONDENSING TMP See Note
SST.B XXX.X F SATURATED SUCTION TEMP See Note
RGT.B XXX.X F COMPR RETURN GAS TEMP See Note
SH.B XXX.X ^F SUCTION SUPERHEAT TEMP See Note
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
PRC.A PRESSURES CIRCUIT A
DP.A XXX.X PSIG DISCHARGE PRESSURE
SP.A XXX.X PSIG SUCTION PRESSURE
PRC.B PRESSURES CIRCUIT B See Note
DP.B XXX.X PSIG DISCHARGE PRESSURE See Note
SP.B XXX.X PSIG SUCTION PRESSURE See Note
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
COOL COOLING SETPOINTS
CSP.1 XXX.X
F COOLING SETPOINT 1 Default: 44 F
CSP.2 XXX.X F COOLING SETPOINT 2 Default: 44 F
CSP.3 XXX.X F ICE SETPOINT Default: 32 F
HEAD HEAD PRESSURE SETPOINTS
H.DP XXX.X F HEAD SETPOINT Default: 95 F
F.O N XXX.X F FAN ON SETPOINT Default: 95 F
F. O FF XXX.X F FAN OFF SETPOINT Default: 72 F
B.OFF XXX.X F BASE FAN OFF DELTA TEMP Default: 23 F
F. D LT XXX.X F FAN STAGE DELTA Default: 15 F
FRZ BRINE FREEZE SETPOINT
BR.FZ XXX.X F BRINE FREEZE POINT Default: 34 F