Carrier 30RAP010-060 Air Conditioner User Manual


 
41
Table 26A — Configuring Outdoor Air and Space Temperature Reset
*4 items skipped in this example.
Table 26B — Configuring Return Temperature Reset
*4 items skipped in this example.
MODE
(RED LED)
KEYPAD
ENTRY
SUB-
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
Outdoor
Air
Space
CONFIGURATION
DISP
UNIT
OPT1
OPT2
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET CRST 2 4
COOLING RESET
TYPE
2 = Outdoor-Air Temperature
4 = Space Temperature
(Connect to TB5-5,6)
RM.NO* 85 °F 72 °F
REMOTE - NO
RESET TEMP
Default: 125.0 F (51.7 C)
Range: 0° to125 F
RM.F 55 °F 68 °F
REMOTE - FULL
RESET TEMP
Default: 0.0° F (-17.7 C)
Range: 0° to 125 F
RM.DG 15 °F 6 °F
REMOTE - DEGREES
RESET
Default: 0° F (0° C)
Range: –30 to 30 F
(–34.4 to -1.1 °C)
MODE
(RED LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
DISP TEST ON/OFF TEST DISPLAY LEDs
UNIT TYPE X UNIT TYPE
OPT1 FLUD X COOLER FLUID
OPT2 CTRL X CONTROL METHOD
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET CRST 3 COOLING RESET TYPE
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM TB6-2,3)
2 = Outdoor-Air Temperature
3 = Return Fluid
4 = Space Temperature
(Connect to TB5-5,6)
RT.NO* 10.0
F
RETURN FLUID - NO
RESET TEMP
Default: 10.0
F (5.6 C)
Range: 0° to10 F COOLER T
RT.F 0.0
F
RETURN FLUID - FULL
RESET TEMP
Default: 0
F (–17.8 C)
Range: 0° to 30 F COOLER
T
RT.DG 10.0 F
RETURN - DEGREES
RESET
Default: 0
F (0 C)
Range: –30 to 30°F (–16.7 to 16.7 C)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER