Carrier 30RAP010-060 Air Conditioner User Manual


 
92
APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
FANS
Fan 1 Relay Off/On FAN_1 N
Fan 2 Relay Off/On FAN_2 N
Cooler/Pump Heater Off/On COOL_HTR N
UNIT ANALOG VALUES
Cooler Entering Fluid snnn.n FCOOL_EWTN
Cooler Leaving Fluid snnn.n FCOOL_LWTN
Lead/Lag Leaving Fluid snnn.n F DUAL_LWT N
TEMPERATURE RESET
4-20 mA Reset Signal nn.n mA RST_MA N
Outside Air Temperature snnn.n FOAT Y
Space Temperature snnn.n F SPT Y
DEMAND LIMIT
4-20 mA Demand Signal nn.n mA LMT_MA N
Demand Limit Switch 1 Off/On DMD_SW1 N
Demand Limit Switch 2 Off/On DMD_SW2 N
CCN Loadshed Signal 0 = Normal
1 = Redline
2 = Loadshed
DL_STAT N
MISCELLANEOUS
Heat Request Off/On HEAT_REQ N
Dual Setpoint Switch Off/On DUAL_IN N
Cooler LWT Setpoint snnn.n FLWT_SPN
Ice Done Off/On ICE_DONE N
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Unit Size nnn tons SIZE
Compressor A1 Size nnn tons SIZE_A1
Compressor A2 Size nnn tons SIZE_A2
Compressor B1 Size nnn tons SIZE_B1
Compressor B2 Size nnn tons SIZE_B2
Suction Superheat Setpt nn.n 9.0 FSH_SP
Number of Fans n FAN_TYPE
Compressor A1 Digital? No/Yes No CPA1TYPE
Maximum A1 Unload Time nn 12 sec MAXULTME
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Cooler Fluid 1 = Water
2 = Med. Brine
1FLUIDTYP
Minimum Load Vlv Select No/Yes No MLV_FLG
CSB Board Enable Dsable/Enable Enable CSB_ENA
Cooler Pump Control Off/On Off CPC
Cooler Pump 1 Enable No/Yes No PMP1_ENA
Cooler Pump 2 Enable No/Yes No PMP2_ENA
Cooler Pmp Periodic Strt No/Yes No PUMP_PST
Cooler Pump Select 0 = Automatic, 1 =
Pump 1, 2 = Pump 2
0 PMP_SLCT
Cooler Pump Shutdown Dly 0 to 10 1 minutes PUMP_DLY
Pump Changeover Hours 10 to 2000 100 hours PMP_DLTA
EMM Module Installed No/Yes No EMM_BRD
Cnd HX Typ: 0=RTPF 1=MCHX 0/1 1 COILTYPE
EXV MOP Set Point nn.n °F MOP_SP
Config Approach Setpoint nn.n °F IAPPROSP