APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Control Method 0 = Switch
2 = Occupancy
3 = CCN
0 CONTROL
Loading Sequence Select 1 = Equal Loading
2 = Staged Loading
1 SEQ_TYP
Lead/Lag Circuit Select 1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
1 LEAD_TYP
Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual CCN occupancy
3 = 4-20 mA input
0 CLSP_TYP
Ramp Load Select Enable/Dsable Enable RAMP_EBL
Heat Cool Select Cool/Heat Cool HEATCOOL
High LCW Alert Limit 2 to 60 60.0 F LCW_LMT
Minutes off time 0 to 15 0 min DELAY
Deadband Multiplier 1.0 to 4.0 1.0 Z_GAIN
Ice Mode Enable Enable/Dsable Dsable ICE_CNFG
Low Sound Mode Select 0 = Disabled
1 = Fan only
2 = Capacity/Fans
0LS_MODE
Low Sound Start Time 00:00 to 23:59 00:00 LS_START
Low Sound End Time 00:00 to 23:59 00:00 LS_END
Low Sound Capacity Limit 0 to 100 100 % LS_LIMIT
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Schedule Number 0 to 99 1 SCHEDNUM
Override Time Limit 0 to 4 0 hours OTL
Timed Override Hours 0 to 4 0 hours OVR_EXT
Timed Override No/Yes No TIMEOVER
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING RESET
Cooling Reset Type 0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
0CRST_TYP
4-20 MA RESET
4-20 – Degrees Reset –30 to 30 0.0 F 420_DEG
REMOTE RESET
Remote – No Reset Temp 0 to 125 125.0 FREM_NO
Remote – Full Reset Temp 0 to 125 0.0 FREM_FULL
Remote – Degrees Reset –30 to 30 0.0 F REM_DEG
RETURN TEMPERATURE RESET
Return – No Reset Temp 0 to 125 10.0 FRTN_NO
Return – Full Reset Temp 0 to 125 0.0 FRTN_FULL
Return – Degrees Reset –30 to 30 0.0 FRTN_DEG
DEMAND LIMIT
Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
0DMD_CTRL
Demand Limit at 20 mA 0 to 100 100 % DMT20MA
Loadshed Group Number 0 to 99 0 SHED_NUM
Loadshed Demand Delta 0 to 60 0 % SHED_DEL
Maximum Loadshed Time 0 to 120 60 minutes SHED_TIM
Demand Limit Switch 1 0 to 100 80 % DLSWSP1
Demand Limit Switch 2 0 to 100 50 % DLSWSP2